10
Protege DIN Rail 8 PGM Output Expander
| Installation Manual
4.2
Wiring Diagram
LED
Description
Power
Green
Correct module input voltage applied.
Off
Incorrect module input voltage applied.
Status
Module successfully registered with controller.
Module attempting registration with controller
Module communication activity.
Fault
Red
Module is in error state. Error code is displayed by
with a delay of 1.5 second between each display cycle.
Number of Flashes
Error Description
1
Unknown Error Code
2
Firmware Version
3
Address Too High
4
Address in Use
5
Controller Secured
6
Serial Number Fault
7
Locked Device
For further details, please refer to the Error Code Display section in the
Installation Manual.
Output 1-8
Off
PGM output is OFF.
Red
PGM output is ON.
Please refer the System Controller Installation Manual for address programming details.
The address of the Output Expander is configured via programming and will require
reference to the module serial number. The serial number can be found on the
identification sticker on the side of the module.
Wiring
AUX WIRING: Min 22AWG Max 16AWG. (Depends on
length and Current consumption). For wire/cable size,
a maximum of 5% voltage drop at the terminals of
the powered device has to be observed.
MODULE NETWORK WIRING: Recommended Belden
9842 or equivalent. (24AWG twisted pair with
characteristic impedance of 120ohm or CAT5e / CAT6
are also supported for Data Transmission when using
ground in the same cable.
Do not use extra wires to
power devices.)
max 900m (3000ft).
PGMs 1-8
Programmable Outputs
The 8 PGM Outputs each have a FORM C
output relay. These PGM’s can be used to
activate bell sirens, lighting circuits, door
locks, relay accessory products and other
automation points.
V+
V-
NO
CN
C
N
O
C
N
C
1K5 OHM
LED
0V
+12V AUX
NA
N+
N-
NB
System Controller or module
supplying power to networked
devices
Next modules
on network
NA
N+
N-
NB
White
Blue
Black
Red
Output Expander
-
Lock Power
Supply
Lock Power
Supply
Electric Locking
Device
+
-
+
-
+
-
1k
8 Ohm 30W
Siren or 1.1A
(Typical)
+
CAUTION:
INCORRECT
WIRING MAY RESULT IN
DAMAGE TO THE UNIT