26
Protege DIN Rail 8 PGM Output Expander
| Installation Manual
ArmorIP detects the reception of any invalid packet on the programmed port as a potential system
compromise attempt. Each compromise attempt sends a notification to the receiver, and logs a
Compromise Attempt event under the Live Panel Events.
The event is sent with the following details:
Account Code as defined in the Serial Receiver settings
Event Code 0x163
Group Code as defined in the Serial Receiver settings
Point Code as defined in the Serial Receiver settings
Refer to the section
Global Settings | Serial Receiver
in the ArmorIP Internet Monitoring Application User's
Manual (227-5500-000).
For UL and ULC installations the Central Station Receiving software must have the Contact ID details as
specified, programmed for the Compromise Attempt event.
Power Supply Mains Power Connection
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The Power Supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
CAN/ULC-S319-05
The Models PRT-CTRL-DIN and PRT-RDM2-DIN are intended to be mounted within the enclosure (refer to
UL/ULC Installation Cabinet Options (see page 23)), installed inside the protected premise, and are
CAN/ULC-S319 Listed for Class I applications only
Exit devices and wiring must be installed within the protected area.
For the Models PRT-CTRL-DIN and PRT-RDM2-DIN, all RS485 and reader terminal connections must be
made using shielded grounded cable.
All readers must be connected with shielded, grounded cable.
A bell or visual indicator used as an arming acknowledgement signal must be listed to a ULC security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to ULC-S533 and
CAN/ULC-S104.
Must be installed with CAN/ULC-S319 listed portal locking device(s) for ULC installations.
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The Power Supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
CAN/ULC-S559-04
Signal Reporting
Any fault of an active communication system shall be annunciated and recorded at the signal receiving
center within 180 s of the occurrence of the fault.
The Report IP and Contact ID services must be programmed and enabled within the Protege System. The
following options are required:
The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start
with the operating system.
Refer to the section
Contact ID
in the ProtegeGX Operator Reference Manual (227-1500-000).
The Report IP Service must be enabled as the primary communication channel, the Service Mode
must be configured to start with the operating system, and the Reporting Protocol must be set to
ArmorIP.
Refer to the section
Report IP
in the ProtegeGX Operator Reference Manual (227-1500-000).
The Trouble Area must be armed. Refer to the section
Trouble Inputs | Areas and Input Types
in the
ProtegeGX Operator Reference Manual (227-1500-000).