184
For L (live cable)
Turn the digital multimeter to 750V AC, use your one hand to hold the metal end, and then the
other hand insert the pen to the L port of the socket. See the following figure. If the multimeter
shows 120, then you can see current live cable connection is standard. If the value is less than
60, then you can see current live cable connection is not proper or it is not the live cable at all.
For N (Neutral cable)
Turn the digital multimeter to 750V AC, use your one hand to hold the metal end, and then the
other hand insert the pen to the N port of the socket. See the following figure. If the multimeter
shows 0, then you can see current N cable connection is standard. If the value is more than 10,
then you can see there is inductive current and the neutral cable connection is not proper. If the
value is 120, then you can know misconnected the neutral cable to the live cable.
Содержание N6 Series
Страница 1: ...ICRealtime N6 Series Standalone DVR User s Manual Version 6 2 0 ...
Страница 51: ...41 Figure 4 25 Figure 4 26 Figure 4 27 ...
Страница 52: ...42 Figure 4 28 Figure 4 29 Figure 4 30 ...
Страница 68: ...58 Figure 5 3 Figure 5 4 Figure 5 5 Figure 5 6 ...
Страница 70: ...60 Please highlight icon to select the corresponding function Figure 5 8 Figure 5 9 Figure 5 10 ...
Страница 76: ...66 Figure 5 16 Figure 5 17 Figure 5 18 5 3 5 3 NTP Setup ...
Страница 116: ...106 Figure 6 11 ...
Страница 145: ...135 Figure 7 43 Figure 7 44 Figure 7 45 Please refer to the following sheet for detailed information ...
Страница 148: ...138 Figure 7 49 Figure 7 50 Figure 7 51 Figure 7 52 ...
Страница 150: ...140 Figure 7 54 Figure 7 55 Figure 7 56 ...
Страница 185: ...175 Maxtor DiamondMax 20 STM3250820AS 250G SATA ...