Electrical installation
14
iMAT 31IFBI-24VDC
Terminal assignment
X1
+
24
D
rn
S
en
G
nd
• +24 supply v 24 Vdc
• Drn Input, triggering of the solenoid valve
internal pull-up resistance (4.4 kOhm) after +24V
input signal "low": valve triggered
input signal "high": valve not triggered
(input open)
• Sen Output, open-drain output
transistor switched through (Gnd potential):
sensor uncovered
transistor open (open-drain):
sensor covered
• Gnd supply voltage 0 V / mass
D
C
O
nl
y
In
pu
t
w
.
P
ul
l-U
p
O
ut
pu
t/
O
pe
n
D
ra
in
0
V
/
M
as
s
1.
1
1.
2
1.
3
1.
4
Note:
Between the terminals and the housing or the condensate connections, there is no galvanic isolation.
The provided 24 VDC voltage must comply with the requirements for protective extra-low voltages (PELV) in
accordance with IEC 60364-4-41.
Tighten the threaded cable connection with a slightly sealing effect.