ICP DAS PMC/PMD Series User Manual
86
The settings are as follow:
Nickname
:
For user to define nicknames for each power meter,
this nickname will be displayed on the “Power Meter
Information” and “Rule Setting” pages.
Description: The Description field provides a space for the user
to make a brief description of this power meter.
Address: The address will be the Modbus address of this
Modbus RTU power meter, please make sure the address setting
is the same as the settings of the module, if the setting is not
accurate, the connection for PMC/PMD to the power meter will
be failed.
Scan Rate: Input the time interval for PMC/PMD to periodically
retrieve the power data of this Modbus RTU Power Meter, the
setting range will be 0 ~ 65535 seconds.
Polling Timeout: The time interval for PMC/PMD to send
command to the Modbus RTU Power Meter and wait for the
response, the unit will be ms. The setting range will be 1-10000
ms.
Retry Interval: The time interval to wait for PMC/PMD to
repeatedly send command again when PMC/PMD sends
command to the Modbus RTU Power Meter and get no response.
The unit will be second. the setting range will be 3 ~ 65535
seconds.
Main Power Meter: When the “Set as main power meter” is
selected, this power meter will be set as main power meter and
the power data of this meter will be displayed on the Main
Power Meter area on the “Power Data Overview” page.
CT/Phase Nickname: For user to define nicknames for each CT
(or phase), this nickname will be displayed on the “Power
Meter Information” and “Rule Setting” pages. For three-phase
power meter, the user could give nicknames to the Phase A/B/C.
After all settings are completed, click “OK” button to return to the
Power Meter List.
Содержание PMC series
Страница 1: ...ICP DAS PMC PMD Power Meter Concentrator Series User Manual Version 3 1 8...
Страница 51: ...ICP DAS PMC PMD Series User Manual 38 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...
Страница 72: ...ICP DAS PMC PMD Series User Manual 59 Figure6 11 Security setting interface of VPN function...
Страница 165: ...ICP DAS PMC PMD Series User Manual 152 The Import of MQTT Topic...
Страница 315: ...ICP DAS PMC PMD Series User Manual 302 B Start the DCON Utility and verify if the COM Port parameters are accurate...