ICP DAS PMC/PMD Series User Manual
294
CT Ratio [3]
PM_SA + 300020
2
Float
1~65535
CT Ratio [4]
PM_SA + 300022
2
Float
1~65535
CT Ratio [5]
PM_SA + 300024
2
Float
1~65535
CT Ratio [6]
PM_SA + 300026
2
Float
1~65535
CT Ratio [7]
PM_SA + 300028
2
Float
1~65535
CT Ratio [8]
PM_SA + 300030
2
Float
1~65535
Modbus Module
This block stores the Modbus TCP/RTU module I/O channel data in PMC/PMD.
The start address of the block is from the SA value. The allocation of the Modbus
address of I / O channel for each Modbus TCP/RTU module is in sequence
arrangement from the module starting address(SA). Please refer to the following
example.
The Modbus RTU module is connected to RS-485-1 of PMC/PMD. Its module
index number is 3. So the SA value of the Modbus RTU module in PMC/PMD is
1000 + (3 - 1) x 1200 = 3400. The Modbus address of the I/O channel of the
module is in sequence arrangement from the module starting address 3400.
The detailed I/O channel information of the module
:
Modbus
Data Model
The Starting Address of
Modbus RTU Module
Continuous Data
Number
Coil Output
11
7
Discrete Input
0
10
Input Register
7
4
(32-bit Floating Point)
Holding Register
20
3
(32-bit Floating Point)
Содержание PMC series
Страница 1: ...ICP DAS PMC PMD Power Meter Concentrator Series User Manual Version 3 1 8...
Страница 51: ...ICP DAS PMC PMD Series User Manual 38 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...
Страница 72: ...ICP DAS PMC PMD Series User Manual 59 Figure6 11 Security setting interface of VPN function...
Страница 165: ...ICP DAS PMC PMD Series User Manual 152 The Import of MQTT Topic...
Страница 315: ...ICP DAS PMC PMD Series User Manual 302 B Start the DCON Utility and verify if the COM Port parameters are accurate...