P6
After finishing the configuration, users can click the button “Save
All Setting” to save the configuration in to the I-7530. If users
would like to recover the parameters to the factory default, click
“Load Default Setting” button to recover all of the configuration
parameters to be default value. Then, users can click the button
“Save All Settings” to save the default parameters in to the
I-7530.
The default values of the parameters of the I-7530 are shown
below.
UART
Baud rate
115200 bps
Data Bit
8
Stop Bit
1
Parity
None
Add Checksum
No
Error Response
No
CAN
CAN Specification
2.0A
CAN Bus Baud rate
125K
CAN ID Filter Acceptance Code
000
CAN ID Filter Acceptance Mask
000
Communication Mode
Communication Mode
Normal
3
I-7530 Communication Test
3.1 Please refer to step 2.1, set the Init / Normal switch on the back
of the I-7530 to the “Normal” position. Then, turn on the power.
The ON LED of the I-7530 will be turned on continuously. That
means that the I-7530 is boot and be in the Run mode.