3
Basics Communication
3.1
EtherCAT Cabling
The cable length between two EtherCAT devices must not exceed 100 m.
Cables and connectors
For connecting EtherCAT devices only Ethernet connections ( plugs) that
meet the requirements of at least category 5 (CAt5) according to EN 50173 or
ISO/IEC 11801 should be used. EtherCAT uses 4 wires for signal transfer.
The pin assignment is compatible with the Ethernet standard (ISO/IEC 8802-3).
3.2
EtherCAT State Machine
The state of the EtherCAT master and slave is controlled via the EtherCAT State
Machine (ESM). The state determines which functions are accessible or executable in
the EtherCAT slave. State changes are typically initiated by requests of the master
and acknowledged by the slave after the successful initialization. In case of an
internal error, the slave automatically changes to a lower state.
Supports four states:
Init (state after Reset)
Pre-Operational
Safe-Operational
Operational