C-12. CL-213 / CL-213-E Modbus Address Mappings (Base 1)
- 213 -
C-12. CL-213 / CL-213-E Modbus Address Mappings (Base 1)
Address Description
Attribute
30001 ~
30008
40001 ~
40008
Analog input value of channel 0 to 7.
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: PM2.5 in 1ug/m
3
,
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5:temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R
40225 ~
40232
High alarm limit of channel 0 to 7,
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: PM2.5 in 1ug/m
3
,
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5:temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R/W
40236 ~
40240
Low alarm limit of channel 3 to 7,
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5: temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R/W
40272
Modbus NetID
Only for Modbus TCP protocol
R/W
30301
40301
Number of the digital input channels
Only for Modbus TCP protocol
R
30311
40311
Number of the digital output channels
Only for Modbus TCP protocol
R
30321
40321
Number of the analog input channels
Only for Modbus TCP protocol
R
30331
40331
Number of the analog output channels
Only for Modbus TCP protocol
R