CL-200 Series User Manual Version 1.2.0 Apr. 2019
- 46 -
Limit
Humidity/ Temperature/ Dew Point.
Beep On
Alarm
Enable/disable beep on alarm for PM2.5 /CO /CO2
/Temp /RH /Dew point
Beep On
Alarm Time
Sets the time for beeping alarm.
Range: 1 ~ 250 (unit: second)
0 = disable the beeping alarm
251 = continue the beeping alarm without stop
30
Set the
Power On Value
and
Safe Value
for the relay output, and the
Host Watchdog
Timeout
timer for RS-485 communication; if a host does not send a command over the
setting time, the Host Watchdog timeout occurs and the relay outputs the status set for
Safe value. The settings for Power On Value and Safe Value are unavailable when any
one setting in the
Alarm Mode
is enabled.
All the settings take effect after clicking the
Update Settings
button.