2.4. Rotary Switch
When users would like to update the module’s firmware or change the CAN baud
rate of the CAN-Logger series, use the rotary switch on the top side to achieve this
purpose.
Figure 2-5 Location of CAN-Logger100/CAN-Logger200 Rotary Switch
There are 16 sections on the rotary switch. They are described on the following
table.
Table 2-2 Description of Rotary Switch
CAN-Logger series CAN Bus data logger devices User Manual (version 1.0.1)
Page: 11
Copyright © 2015 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
Switch Value Description
0
Set CAN Bus baud rate to 10 kbps
1
Set CAN Bus baud rate to 20 kbps
2
Set CAN Bus baud rate to 50 kbps
3
Set CAN Bus baud rate to 100 kbps
4
Set CAN Bus baud rate to 125 kbps
5
Set CAN Bus baud rate to 250 kbps
6
Set CAN Bus baud rate to 500 kbps
7
Set CAN Bus baud rate to 800 kbps
8
Set CAN Bus baud rate to 1 Mbps
9
Set CAN Bus baud rate to user-defined baud rate which is
configured by CAN-Logger utility.
A~E
N/A
F
Set CAN-Logger device into firmware upgrade mode.