CAN-8x23 user’s manual (Revision 3.20, Ma r/08/2012) ------
172
2h
transmission type
UNS IGNED 8
RW
FFh
RxPDO Mapping Communication Entries
Idx
Sidx
Description
Ty pe
Attr
Default
1600h
0h
largest sub-index supported for
“receive PDO mapping”
UNS IGNED 8
RO
8
1h
write digital output 1h to 8h
UNS IGNED 8
RW
6200 0108h
2h
write digital output 9h to 10h
UNS IGNED 8
RW
6200 0208h
3h
write digital output 11h to 18h
UNS IGNED 8
RW
6200 0308h
4h
write digital output 19h to 20h
UNS IGNED 8
RW
6200 0408h
5h
write digital output 11h to 28h
UNS IGNED 8
RW
6200 0508h
6h
write digital output 19h to 30h
UNS IGNED 8
RW
6200 0608h
7h
write digital output 11h to 40h
UNS IGNED 8
RW
6200 0708h
8h
write digital output 19h to 48h
UNS IGNED 8
RW
6200 0808h
1601h
0h
largest sub-index supported for
“receive PDO mapping”
UNS IGNED 8
RO
4
1h
write analog out put 1h
UNS IGNED 16
RW
6411 0110h
2h
write analog out put 2h
UNS IGNED 16
RW
6411 0210h
3h
write analog out put 3h
UNS IGNED 16
RW
6411 0310h
4h
write analog out put 4h
UNS IGNED 16
RW
6411 0410h
1602h
0h
largest sub-index supported for
“receive PDO mapping”
UNS IGNED 8
RO
4
1h
write analog out put 5h
UNS IGNED 16
RW
6411 0510h
2h
write analog out put 6h
UNS IGNED 16
RW
6411 0610h
3h
write analog out put 7h
UNS IGNED 16
RW
6411 0710h
4h
write analog out put 8h
UNS IGNED 16
RW
6411 0810h
1603h
0h
largest sub-index supported for
“receive PDO mapping”
UNS IGNED 8
RO
4
1h
write analog out put 9h
UNS IGNED 16
RW
6411 0910h
2h
write analog out put Ah
UNS IGNED 16
RW
6411 0A10h
3h
write analog out put Bh
UNS IGNED 16
RW
6411 0B10h
4h
write analog out put Ch
UNS IGNED 16
RW
6411 0C10h
1604h
0h
largest sub-index supported for
“receive PDO mapping”
UNS IGNED 8
RO
---
1h
---
---
RW
---
...
...
...
...
...