CAN-8x23 user’s manual (Revision 3.20, Ma r/08/2012) ------
196
I-8017HS/I-8017HW
Analog Input Type Definition
Range Code
(Hex)
Output Range
Data Format
Max Value
Min Value
0
(default)
-10 to 10V
Input Range
+10.000 V
-10.000 V
Hexadecimal
1FFF
2000
1
-5 to 5V
Input Range
+5.000 V
-5.000 V
Hexadecimal
1FFF
2000
2
-2.5V to +2.5V
Input Range
+2.500 V
-2.5000 V
Hexadecimal
1FFF
2000
3
-1.25V to +1.25V
Input Range
+1.250 V
-1.250 V
Hexadecimal
1FFF
2000
4
-20 mA to +20 mA
Input Range
+20.000 mA -20.000 mA
Hexadecimal
1FFF
2000
I-8080/ 8084W
Counter Input Type Definition
Range Code
(Hex)
Counter Type
Channel
number
Max Value
Min Value
0
*1
Dir/Pulse Counter
4
2147483647
-2147483648
1FFFFFFF
80000000
1
*1
Up/Down Counter
4
2147483647
-2147483648
1FFFFFFF
80000000
2
Frequency
8
-
-
-
-
3
(default)
Up Counter
8
4294967295
0
FFFFFFFF
00000000
4
*1
(for I-8084W)
AB Phase
4
2147483647
-2147483648
1FFFFFFF
80000000
Note:
*1: The sub-index of all parameters and input channels are still 8, but the sub-index 1 is