Tip 1:
Error Code 13 & 14 Potential Causes
High pressure switch opens due
to high discharge pressure.
High pressure switch opens due
to high discharge pressure 3
consecutive times.
OR
IM-Series
Error Codes
44
Water:
•
Is water supply to condenser insufficient?
(WATER COOLED ONLY)
•
Is water supply to condenser below 20psi?
(WATER COOLED ONLY)
•
Is there poor air circulation?
•
Is the condenser air filter dirty and in need of cleaning?
•
Is the air condenser dirty and in need of cleaning?
•
Is the air condenser blocked.
•
Does the condenser fan motor have power from PCB?
•
Is the condenser fan motor capacitor faulty/bad?
•
Is the condenser fan motor faulty/bad?
•
Is the fan blade broken?
Air:
Refrigeration:
•
Is the system properly charged?
•
Is the hot gas solenoid valve open/leaking?
•
Is the headmaster stuck in bypass?