Tip 1:
Error Code 1 or 3 Potential Causes
Evap temp 32°F or higher
after 30 minutes in freeze.
Refrigerant:
•
Is the machine overcharged?
•
Is hot gas leaking past hot gas solenoid valve?
•
Is TXV flooding the evaporator with refrigerant?
•
Headmaster stuck in bypass? (REMOTE ONLY)
Electrical:
•
Is suction line thermistor open or shorted?
•
Defective fan cycling control?
Evap temp exceeds 23°F
after 30 minutes in freeze.
OR
Water:
•
Is water inlet solenoid valve leaking by?
•
Water regulator restricting water flow?
(WATER-COOLED ONLY)
IM-Series
Error Codes
41
Air:
•
Is the air filter or condenser clogged?
•
Is the condenser discharge air being recycled back
into the condenser?