Owner's Manual
Wall Guide
The Wall Guide is used as a lateral guide
to resist lateral load. It does not carry any
vertical chimney weight. It also maintains
the minimum clearance to combustibles.
(which can be adjusted from 2" to 6") It
can also be used to stabilize the chimney
horizontally.
The Wall Guide must be installed on the
chimney’s outer shell not on the outside
finishing band. The locking band must be
able to move without interfering with the
guide when thermal expansion occurs.
The Wall Guide collar is secured on the
outer casing of the chimney with the
collar’s 2 screws. The square angles must
be anchored to the wall (combustible walls
are allowed, at least 3x wood screws #10 x
2" per bracket) with a minimum of 3
anchors on each side. (by others)
See
Table 7
for Maximum Vertical Spacing
between 2 Supports or Guides (
MVS)
Figure 12
Figure 13
Floor Guide
The Floor Guide is mainly used as a
chimney stabilization device at floor
penetrations. It does not carry any vertical
chimney weight. It also maintains the
minimum clearance to combustibles.
The Floor Guide must be installed on the
chimney’s outer shell not on the outside
finishing band. The locking band must be
able to move without interfering with the
guide when thermal expansion occurs.
The Floor Guide collar is secured on the
outer casing of the chimney with the
collar’s 2 screws. The 4 square brackets
must be anchored to the floor (combustible
floors are allowed, at least 4x wood screws
#10 x 2" per bracket) with a minimum of 4
anchors per bracket. (by others)
See
Table 7
for Maximum Vertical Spacing
between 2 Supports or Guides (
MVS)
Figure 14
Figure 15