background image

Mounting in the

 vertical

 orientation shown above IS NOT ADVISABLE 

for LPHW units due to the actuator being below the valve. 

Service/Maintenance Access – Unit must be installed with a 

minimum of unit depth as additional clearance i.e DS1A-NES 

either allow 233mm above or below unit.

For systems which include supply fans with heating other than 

where the BMS (0-10V) has control, the appropriate user control is

 

required (i.e. ES-LCD or ES-CI

)

.

The EMC Directive 
20

1

4/

30

/E

U

  

The Low Voltage 
Directive 
20

14/3

5/E

U

18. 10. 17. Leaflet Number 671679

DAVE Supply Fans (ES Models) 50/60Hz

For Internal and External use

Installation & Maintenance Instructions

Assembly with
base frame.

Palletised.

Forklift.

Slings via spreaders fitted to unit
with base frame.

Please note that above images are
examples of typical lifting methods. 
Actual unit lifting plan and risks
must be assessed by competent 
personnel before moving the unit.

DS1A-NES

H

| |

 

|

 

|

|

|

1 2

 

3

 

4 5

6

1. 

DAVE Range 

2. 

Supply fan

3. 

Case size (1-7)

4. 

L = LPHW Coil/valve
E = Electric heater

   

= No heater

5. 

ES

 

= Ecosmart control

6. No suffix = 50Hz

H = 60Hz 

Front Elevation

Control

Airflow

DAVE Supply Fans

The Dave range of in-line backward curve fans consisting of 
9 duty sizes with a maximum of 1.1m

3

/s (1100l/s).

Units are manufactured from aluzinc, rectangular in section and have
circular rigid spigots at each end. All units are supplied with fixing
brackets designed to simplify installation.

1.0 Fan Unit Coding Descriptions

2.0 Handling

Always handle the units carefully to avoid damage and distortion.
Care must be taken to ensure any slings used for hoisting do not
damage the casing or the control module components. 

Note: The weight of the unit is on the rating plate.

Figure 1: Typical lifting methods.

3.0 Installation

Installation must be carried out by competent personnel, in 
accordance with good industry practice, the appropriate authority

 

and in conformance with all statutory and governing regulations. 

Access to the unit for maintenance is via the top or bottom lid,

 

therefore this should be taken into account before installation 
takes place (See important note below).

Figure 2: Mounting in t

he vertical

 orientation

 below

 is not advisable 

(LPHW units only).

Units are supplied complete with four support mounting brackets 
for quick and easy installation, either surface mounted or suspended
with drop rods. 

Figure 3: Units supplied with four mounting brackets with 
1 x M8 hole in each.

External units must not be installed at an angle over 5° from 

the horizontal.

Nuaire: A Trading Division of Polypipe Limited

  

Western Industrial Estate Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk

1

Содержание DAVE Series

Страница 1: ... are manufactured from aluzinc rectangular in section and have circular rigid spigots at each end All units are supplied with fixing brackets designed to simplify installation 1 0 Fan Unit Coding Descriptions 2 0 Handling Always handle the units carefully to avoid damage and distortion Care must be taken to ensure any slings used for hoisting do not damage the casing or the control module componen...

Страница 2: ...5 190 DS3A EES H 1005 780 345 200 430 155 155 DS4A NES H 1005 840 370 250 370 150 100 DS4A LES H 1005 840 370 250 430 175 190 DS4A EES H 1005 840 370 250 430 155 155 DS4HA NES H 1005 840 370 250 370 150 100 DS4HA LES H 1005 840 370 250 430 175 190 DS4HA EES H 1005 840 370 250 430 155 155 DS5A NES H 1155 1110 1110 984 410 315 370 150 100 DS5A LES H 1155 984 410 315 430 175 190 DS5A EES H 1155 984 4...

Страница 3: ...valve to a fully open position to allow full water flow through the coil and the main PCB will close the Heat demand contacts These contacts could be used to send a signal to activate the boiler and or valve to open to provide heat if not already doing so 4 1 2 Port Pressure Independent Balancing Control Valve Setting Instruction Fig 6 Remove Actuator Fig 7 Unlock Adjusting Collar Units 1 2 2H DN2...

Страница 4: ...el details Note A Commissioning Procedure document leaflet No 671153 is available on request from Nuaire Tel 029 2088 5911 The Control Module Fig 12 The BMS connection is made with a plug in connector via the socket See figure 13 To ensure the connection is made only by suitably qualified and authorised personnel the plug is not supplied It is available from R S Components Part No 403 875 or Farne...

Страница 5: ...ater Neutral Thermistor T Thermistor R Signal 0V Signal VE OIP 5V Note Customer connections for electric heater 40amp draw E N L L N E Heater Temperature Settings Note Customer connections for fan and control 5amp draw max 5 18 10 17 Leaflet Number 671679 Notes Local isolator by others All inter connections between circuit boards blowers and sensors are made at the factory Remove link wire if swit...

Страница 6: ...OL COOLING CONTROL 0V SETPOINT 0 10V 10V 0V DEADBAND 0 10V 10V AUTO HEAT COOL OFF ON COOL SENSOR ACTUATOR CONTROL WHITE ACTUATOR CONTROL BLACK ACTUATOR CONTROL RED Note Customer connections for fan and control 5amp draw max 6 18 10 17 Leaflet Number 671679 Notes Local isolator by others All inter connections between circuit boards blowers and sensors are made at the factory Remove link wire if swi...

Страница 7: ...nce Ensure all control components are secure and clean refit the cover Lubrication Motors are fitted with sealed for life bearings and do not require any lubrication Filter care replacement The filter where applicable will require cleaning on a regular basis The frequency of the cleaning operation will depend on the site conditions 7 0 Fan Components see fig 18 Key Components A Lid Base B Attenuat...

Страница 8: ...es office for further details 9 0 Spares for Dave Supply fans Spare parts and replacement components are available from Nuaire Ltd Please contact us on the numbers below for further details G4 Filter Unit Size Replacement Part No DS1A ES D1A G4FILTERKIT DS2A ES D2A G4FILTERKIT DS2HA ES D2HA G4FILTERKIT DS3A ES D3A G4FILTERKIT DS4A ES D3A G4FILTERKIT DS4HA ES D4HA G4FILTERKIT DS5A ES D5A G4FILTERKI...

Страница 9: ...nged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orientation 4 2 Where installation accessories...

Отзывы: