Model VIP+
18
Owner's Manual
Combustible Roof Penetration – 1400°F Chimney (UL 2561 & ULC C-959 Listings)
* The instructions in this section are valid for appliances with venting flue gases at temperatures not exceeding 760°C (1400°F) under continuous
operating conditions from gas, liquid, oil or solid fuel fired appliances. Also complies with brief operation (maximum 10 minutes) at temperatures not
exceeding 906°C (1700°F).
The Flat Roof Penetration requires the use of a
Ventilated Radiation Shield
, a
Floor Guide
and a
Flashing Kit
. The Flat Roof Penetration
assembly instructions are primarily used for Engines or High Temperature Applications where a chimney section passes through a roof made of
combustible material. It is designed to be installed on a flat roof (or roof curb) 4" to 15" high. The Radiation shield sleeve must extend under the roof
by a minimum of 3”. The roof framing dimensions are presented in
Table 8
in the previous Section.
1. The Radiation Shield is inserted into the framing hole from above the roof and secured with screws on the roof top or roof curb.
2. The Floor Guide is secured to the top roof (or roof curb) using 4 wood screws #10 x 2" wood screws per bracket.
3. The Flat Flashing is then lowered above the Floor Guide and the Storm Collar secured to the chimney section with the screws supplied.
Flat Roof
Figure 29
Roof Curb
Figure 30