Siemens FLN Details
10.1
Node Addressing
ASD parameter
ASD Number
selects the FLN node address. Valid addresses
are 0 – 98.
NOTE
that the factory default value for
ASD Number
is
0
.
10.2
Network Characteristics
No configuration is necessary. The network characteristics are predetermined
according to the FLN specification.
10.3
Timeout Behavior
If a timeout time is selected via
Ext Comm Cfg #3
, then after the designated
period of network inactivity frequency command (#28) and ASD command
word-related objects (#30 and #33
∼
#39) will be automatically written with a
“failsafe” value of 0.