Supported Objects
Table 4 provides a listing of the Metasys objects supported by the interface.
Table 4: Supported Objects
NPT
1
NPA
2
Units
Description
Range/Value
AI 1 Hz
Output
frequency
0.00
∼
400.00
AI 2 %
Load
current
0.00
∼
327.67
AI 3 %
Output
voltage
0.00
∼
327.67
AI 4 kW
Input
power
0.00
∼
655.35
AI 5
kWh
System
energy
0.00
∼
42.9x10
6
AI 6 %
RR
analog
input
0.00
∼
100.00
AI
7
%
VI / II analog input
0.00
∼
100.00
AI 8 --
Fault
code
0
∼
255
AI 9 --
Ext Comm Cfg #5
reference
0
∼
65535
AI 10 --
Ext Comm Cfg #6
reference
0
∼
65535
BI
1
--
Run / stop status
0 = stopped
1 = running
BI
2
--
Forward / reverse status
0 = forward
1 = reverse
BI 3 --
Fault
status
0 = not faulted
1 = faulted
BI
4
--
“F” programmable input terminal status
0 = OFF
1 = ON
BI
5
--
“R” programmable input terminal status
0 = OFF
1 = ON
BI
6
--
“ST” programmable input terminal status
0 = OFF
1 = ON
BI
7
--
“RES” programmable input terminal status
0 = OFF
1 = ON
BI
8
--
“S1” programmable input terminal status
0 = OFF
1 = ON
BI
9
--
“S2” programmable input terminal status
0 = OFF
1 = ON
BI
10
--
“S3” programmable input terminal status
0 = OFF
1 = ON
BI
11
--
“S4” programmable input terminal status
0 = OFF
1 = ON
BI
12
--
“OUT1” programmable output terminal status
0 = OFF
1 = ON
BI
13
--
“OUT2” programmable output terminal status
0 = OFF
1 = ON
BI
14
--
“FL” programmable output terminal status
0 = OFF
1 = ON
AO 1 Hz
Frequency
command
0.00
∼
400.00
AO
2
--
Preset speed selection
0
∼
15
AO 3 --
Ext Comm Cfg #7
reference
0
∼
65535
AO 4 --
Ext Comm Cfg #8
reference
0
∼
65535
BO
1
--
Run / stop command
0 = stop
1 = run
BO
2
--
Forward / reverse selection
0 = forward
1 = reverse
BO
3
--
Emergency off command
0 = no action
1 = emerg. off