Environment
Temperature
Altitude
Relative
humidity
Maximum wet
bulb
temperature
Shipping
-20°C to 60°C
(-4°F to 140°F)
0 to 10668 m
(0 to 34991 ft)
5% to 100%
condensing, but
no precipitation
29°C (84°F)
Environment requirements with redundant ac power
Ensure that your environment falls within the following ranges if you are using
redundant ac power.
Environment
Temperature
Altitude
Relative
humidity
Maximum wet
bulb
temperature
Operating in
lower altitudes
15°C to 32°C
(59°F to 89°F)
0 to 914.4 m
(0 to 3000 ft)
20% to 80%
noncondensing
23°C (74°F)
Operating in
higher altitudes
15°C to 32°C
(50°F to 88°F)
914.4 to 2133.6
m
(3000 to 7000 ft)
20% to 80%
noncondensing
23°C (74°F)
Turned off
10°C to 43°C
(50°F to 110°F)
0 to 2133.6 m
(0 to 7000 ft)
20% to 80%
noncondensing
27°C (81°F)
Storing
1°C to 60°C
(34°F to 140°F)
0 to 2133.6 m
(0 to 7000 ft)
5% to 80%
noncondensing
29°C (84°F)
Shipping
-20°C to 60°C
(-4°F to 140°F)
0 to 10668 m
(0 to 34991 ft)
5% to 100%
condensing, but
no precipitation
29°C (84°F)
Preparing your environment
The following tables list the physical characteristics of the SAN Volume Controller
2145-8F4 and SAN Volume Controller 2145-8F2 nodes.
Dimensions and weight
Ensure that space is available in a rack that is capable of supporting the node.
Height
Width
Depth
Maximum weight
43 mm
(1.69 in.)
440 mm
(17.32 in.)
686 mm
(27 in.)
12.7 kg
(28 lb)
Additional space requirements
Ensure that space is also available in the rack for the following additional space
requirements around the node.
Location
Additional space
requirements
Reason
Left and right sides
50 mm (2 in.)
Cooling air flow
Back
Minimum:
100 mm (4 in.)
Cable exit
Chapter 1. SAN Volume Controller overview
3
Содержание SAN Volume Controller 2145-8F2
Страница 2: ......
Страница 8: ...vi IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 24: ...xxii IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 54: ...30 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 78: ...54 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 80: ...56 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 88: ...64 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 95: ......
Страница 96: ...Printed in USA GC27 2221 00...