Main power connector
2
Communication port
3
Load segment 2 receptacle
Attention:
Ensure that you comply with the following requirements:
v
The voltage supplied to the 2145 UPS-1U must be 200 - 240 V single phase.
v
The frequency supplied must be 50 or 60 Hz.
Notes:
a.
The 2145 UPS-1U has an integrated circuit breaker and does not
require external protection.
b.
The 2145 UPS-1U is intended to maintain power on SAN Volume
Controller nodes until data can be saved to the local hard-disk drive.
Only SAN Volume Controller nodes can be plugged into the 2145
UPS-1U or the SAN Volume Controller cluster malfunctions.
8.
Press and hold the on/off button (
7
in Figure 36) for approximately five
seconds. You might need a pointed device, such as a screwdriver, to press the
on/off button. The front panel indicators cycle through a startup sequence
while the 2145 UPS-1U conducts a self-test.
When the self-test is complete, the power-on indicator
6
and the load
indicators (
1
and
2
) illuminate to indicate that power is being supplied by
the 2145 UPS-1U. The 2145 UPS-1U is now in normal mode, and is charging its
battery. If the battery indicator
4
is on and the alarm is sounding, the voltage
range setting might not be correct. When a SAN Volume Controller is
connected to the 2145 UPS-1U, the SAN Volume Controller automatically
adjusts the voltage range setting. Take no action for this alarm condition unless
it persists for more than five minutes after a SAN Volume Controller has been
connected to this 2145 UPS-1U and turned on.
9.
Repeat all of these steps to install additional 2145 UPS-1U units.
1yz09b
1
2
3
Figure 35. 2145 UPS-1U (rear view)
+ -
LOAD1
LOAD2
1yyzvm
6
7
8
1
2
3
4
5
Figure 36. 2145 UPS-1U front-panel assembly
Chapter 4. Installing the SAN Volume Controller 2145-8F4 or the SAN Volume Controller 2145-8F2 hardware
41
Содержание SAN Volume Controller 2145-8F2
Страница 2: ......
Страница 8: ...vi IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 24: ...xxii IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 54: ...30 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 78: ...54 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 80: ...56 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 88: ...64 IBM System Storage SAN Volume Controller Models 2145 8F2 and 2145 8F4 Hardware Installation Guide...
Страница 95: ......
Страница 96: ...Printed in USA GC27 2221 00...