Symptom
Cause
Recommended action
If the ambient air is below 25ºC
(77ºF), and the fans are observed
to increase in speed, then some
restriction on airflow maybe
causing additional internal
temperature rise.
Note: This is not a fault
condition.
The first stage in the thermal
control process is for the fans to
automatically increase in speed
when a thermal threshold is
reached. This may be caused by
higher ambient temperatures in
the local environment, and may
be perfectly normal.
Note: This threshold changes
according to the number of disks
and power supplies fitted.
1. Check the installation for any
airflow restrictions at either
the front or back of the
enclosure. A minimum gap of
25 mm (1") at the front and
50 mm (2") at the rear is
recommended.
2. Check for restrictions due to
dust build-up. Clean as
appropriate.
3. Check for excessive re-
circulation of heated air from
rear to front. Use of the
enclosure in a fully enclosed
rack is not recommended.
4. Verify that all blank modules
are in place.
5. Reduce the ambient
temperature.
Thermal alarm
Symptom
Cause
Recommended action
1. Front panel Module Fault LED
is amber.
2. Fan Fail LED is illuminated on
one or more PSUs.
Internal temperature exceeds a
preset threshold for the
enclosure.
1. Verify that the local ambient
environment temperature is
within the acceptable range.
2. Check the installation for any
airflow restrictions at either
the front or back of the
enclosure. A minimum gap of
25 mm (1") at the front and
50 mm (2") at the rear is
recommended.
3. Check for restrictions due to
dust build-up. Clean as
appropriate.
4. Check for excessive re-
circulation of heated air from
rear to front. Use of the
enclosure in a fully enclosed
rack is not recommended.
5. If possible, shut down the
enclosure and investigate the
problem before continuing.
60 IBM ESS expansion: Hardware Installation and Maintenance Guide - Model 106
Содержание 106
Страница 1: ...IBM ESS expansion Version 5 3 5 Hardware Installation and Maintenance Guide Model 106 IBM SC27921101...
Страница 6: ...Russia Electromagnetic Interference Class A Statement 100 Homologation statement 100 vi...
Страница 12: ...xii...
Страница 18: ...xviii IBM ESS expansion Hardware Installation and Maintenance Guide Model 106...
Страница 20: ...2 IBM ESS expansion Hardware Installation and Maintenance Guide Model 106...
Страница 44: ...26 IBM ESS expansion Hardware Installation and Maintenance Guide Model 106...
Страница 53: ...Figure 28 CMA attachment aligned with outer slide Figure 29 Panhead screws Chapter 4 Installation 35...
Страница 84: ...66 IBM ESS expansion Hardware Installation and Maintenance Guide Model 106...
Страница 100: ...82 IBM ESS expansion Hardware Installation and Maintenance Guide Model 106...
Страница 108: ...90 IBM ESS expansion Hardware Installation and Maintenance Guide Model 106...
Страница 119: ......
Страница 120: ...IBM SC27921101...