Figure 26
Pipes extend completely through the wall (Vertical orientation shown)
Ensure that the vent termination location does not exceed the allowed maximum
equivalent vent length, including the allowance for the SST.
Install multiple vent SST installations level with one another and maintain at least the
minimum separation distances shown below. The terminals shall not be stacked vertically.
Figure 27 :
Minimum separation for multiple vent
installation - vertical orientation
Figure 28 :
Minimum separations for multiple vent
installation - horizontal orientation
Caution
Take care installing Concentric Side Wall Termination kits when the outdoor
temperature drops below 5°F/-15°C. Possible blockage of the combustion air intake
can occur when the outdoor temperature drops below this temperature.
Approved PVC Side Wall Termination kits are listed below:
Ipex # 196984 2 inch
Ipex # 196985 3 inch
Figure 29
Approved PVC Side Wall Termination configuration
35
3.7.6 Sidewall vent termination
Содержание SL SERIES
Страница 8: ...Intentionally left empty...
Страница 14: ...Intentionally left empty...
Страница 66: ...Figure 49 Electric wiring connections 62 Section Installation...
Страница 78: ...Intentionally left empty...
Страница 92: ...Intentionally left empty...
Страница 105: ...101 Appendices Wiring diagrams V 10 Controller electrical diagram Figure 52 Controller electrical diagram...
Страница 106: ...Internal wiring diagram Figure 53 Internal wiring diagram 102 Section Appendices...
Страница 107: ...Sequence of Operation Figure 54 Sequence of Operation 103 Sequence of Operation...
Страница 109: ...105 Exploded views of boiler parts...
Страница 114: ...110 Section Appendices...
Страница 118: ...Item Description Part Quantity 200 Fan Coupler 250 749 P 347 1 205 Fan Coupler O ring 150 254 1 114 Section Appendices...
Страница 122: ...Intentionally left empty...