Ensure the supplied trap is
correctly installed and filled with
water.
When required, add (and maintain
in good condition) a neutralization
tank. For information on installing
a condensate neutralizer, see
The condensate trap must be
installed on the drain connection at
the base of the boiler. The
condensate drain must be piped to
within 1" of a drain or connected to
a condensate pump. The drainage
line must slope down to the drain
at a pitch of ¼" per foot so condensate runs towards the drain.
1.
Remove the boiler door.
2.
To remove the condensate retainer,
undo the two wing nuts. Retain for later.
38
Section: Installation