INSTALLATION AND OPERATION INSTRUCTIONS
2-6
HC SERIES BOILERS
HC 13-50, HC 23-84, HC 29-106, HC 33-124, HC 20-125, HC 33-160
o.
DHW ECO mode Learning Days
3 days
Range 1 to 10: Number of days the ECO mode
uses to learn the Tankless DHW usage habits.
Rolling counter. If set to 0 Opentherm will control
Eco Comfort Mode Occupied or Un-Occupied.
P
Space Heating Delay after
the boiler reaches the target
temperature
2 min
Range 0 – 15 min: The boiler will remain off for X
min to help reduce short cycling when the heating
load is smaller than the min firing rate.
P.
Heat Exchanger Size Reference
Model Dependent
HC 13-50 / HC 23-84 = 24
HC 29-106 = 30
HC 33-124, HC 20-125 and HC 33-160 = 36
PARAMETER 1
SETTINGS
LOAD PRIORITY:
0 = HIGHEST
PARAMETER NUMBER 1: DETAILED DESCRIPTION
0
0 = Tankless DHW
1 = Space Heating
DC Models – Both Space Heating and Tankless DHW
•
Internal Boiler Pump is enabled with a call for Space Heating
•
Internal Boiler Pump is disabled with a call for Tankless DHW
1
0 = Indirect DHW Tank Sensor
or Aquastat
1 = Space Heating
HC Models – Space Heating and Indirect DHW Tank. DHW must be
turned on by pressing the Tap
twice. Bottom LED must be ON.
•
Aquastat or Sensor connected to X4.9 and X4.10
•
Internal Boiler Pump is enabled for both Space Heating and for DHW
heating
•
External Pump Terminals 4,5,6 (120Vac - 1Amp Max) enabled with a
call for DHW
2
0 = Tankless DHW
DC Models – Tankless DHW Only
•
DHW only, Space Heating Disabled
•
Internal Pump disabled
3
0 = Space Heating
HC Models – Space Heating Only
•
Internal Boiler Pump is enabled with a call for Space Heating
4
0 = DHW Storage Tank Sensor
or Aquastat
1 = Space Heating
DC Models – Space Heating and Tankless DHW with a Storage Tank.
DHW must be turned on by pressing the Tap
twice. Bottom LED
must be ON.
•
Aquastat or Sensor connected to X4.9 and X4.10
•
External Pump Terminals 4,5,6 (120Vac - 1Amp Max) enabled with a
call for DHW
•
Internal Boiler Pump is enabled with a call for Space Heating
•
Internal Boiler Pump is disabled with a call for Tankless DHW
•
External DHW Pump is enabled with a call for Tankless DHW
5
0 = DHW Storage Tank Sensor
or Aquastat
DC Models – Tankless DHW with a Storage Tank Only. DHW must be
turned on by pressing the Tap
twice. Bottom LED must be ON.
•
Space Heating is disabled
•
Aquastat or Sensor connected to X4.9 and X4.10
•
External Pump Terminals 4,5,6 (120Vac - 1Amp Max) enabled with a
call for DHW
•
Internal Boiler Pump disabled
•
Internal Boiler Pump is disabled with a call for Tankless DHW
6
0 = Tankless DHW
1 = Indirect DHW Tank Sensor
or Aquastat
2 = Space Heating
DC Models – Space Heating, Indirect DHW Tank and Tankless DHW
•
External Pump Terminals 4,5,6 (120Vac - 1Amp Max) enabled with a
call for DHW
•
Internal Boiler Pump is enabled for both Space Heating and for Indirect
DHW
•
Internal Boiler Pump is disabled with a call for Tankless DHW
NOTE:
The control displays codes that include upper and lower case letter and a combination with a period after the letter.
Example: C, c., c are all valid parameter codes. When adjusting settings, double check that you are in the correct parameter.