6.2 Testing the ignition safety shutoff
To test the ignition system safety shutoff device:
1. With the boiler in operation, shut off the gas control valve directly outside the boiler case.
2. Ensure that the boiler has purged, attempted to re-light three times, has shut off and the
appropriate error information is displayed on the controller.
3. The error is displayed after testing the ignition safety shutoff.
4. To restart the boiler, reset the power or on the
touchscreen
controller
's
Main Menu
, tap
Diagnostics
>
Advanced
Diagnostics
>
Clear Errors
>
Yes
>
OK
.
6.3 Commissioning
The EX modulating boilers are factory calibrated to operate with
natural gas (or propane if desired) at sea level. The gas-air ratio or
zero-offset adjustment screw may need adjusting to attain optimum
combustion results. Note that only qualified technicians using
properly functioning and calibrated combustion analyzing equipment
should perform a mixture adjustment.
6.3.1 Checking a boiler's fuel source
This boiler model can burn either natural gas or propane if equipped with the correct fuel-air
metering device. Examine the rating plate of the boiler to ensure it is configured for the fuel you
are using. If the boiler is configured for natural gas, but needs to be converted to propane, use the
conversion kit (sold separately by IBC) to install the appropriate fitting(s) and adjust the gas
valve accordingly. See
for the required conversion kit.
The
touchscreen controller
will automatically detect the installation’s altitude and make the
appropriate adjustments to operate the boiler up to 4,500 feet in elevation without de-ration. The
boiler will automatically de-rate at altitudes above 4,500 feet.
66
Section: Boiler operation
Содержание EX Series
Страница 62: ...Intentionally left empty...
Страница 80: ...Intentionally left empty...
Страница 121: ...Appendices Wiring diagrams Figure 73 Controller electrical diagram 119 Appendices...
Страница 122: ...Figure 74 Internal wiring diagram EX 400 and EX 500 models 120 Section Appendices...
Страница 123: ...Figure 75 Internal wiring diagram EX 700 and EX 850 models 121 Wiring diagrams...
Страница 124: ...Figure 76 Sequence of Operation 122 Section Appendices...
Страница 126: ...Intentionally left empty...
Страница 128: ...126 Boiler parts diagram EX 400 and EX 500...
Страница 132: ...130 Boiler parts diagram EX 700 and EX 850...