E
Clearance to unventilated soffit
*
*
F
Clearance to outside corner
6' (1.83 m)*
6' (1.83 m)*
G
Clearance to inside corner
6' (1.83 m)
6' (1.83 m)*
H
Clearance to each side of center line
extended above meter/regulator assembly
*
3' (91 cm) within a
height 15' above the
meter/ regulator
assembly
I
Clearance to service regulator vent outlet
*
6' (1.83 m)
J
Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
other appliance
4' (1.2 m) below or
to side of opening;
1' (30 cm) above
opening
3' (91 cm)
K
Clearance to mechanical air supply inlet
*
6' (1.83 m)
L
Do not terminate above paved sidewalk or
paved driveway
Slip hazard due to
frozen condensate
Slip hazard due to
frozen condensate
M
Clearance under veranda, porch, deck or
balcony
*
12" (30 cm)
3
Table 5
Vent/air inlet termination clearances
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
2
In accordance with the current CAN/CSA-B149 Installation Codes.
3
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal, and underside of
veranda, porch, deck or balcony is greater than 1' (30 cm).
29
3.5.7 Sidewall vent termination
Содержание EX Series
Страница 62: ...Intentionally left empty...
Страница 80: ...Intentionally left empty...
Страница 121: ...Appendices Wiring diagrams Figure 73 Controller electrical diagram 119 Appendices...
Страница 122: ...Figure 74 Internal wiring diagram EX 400 and EX 500 models 120 Section Appendices...
Страница 123: ...Figure 75 Internal wiring diagram EX 700 and EX 850 models 121 Wiring diagrams...
Страница 124: ...Figure 76 Sequence of Operation 122 Section Appendices...
Страница 126: ...Intentionally left empty...
Страница 128: ...126 Boiler parts diagram EX 400 and EX 500...
Страница 132: ...130 Boiler parts diagram EX 700 and EX 850...