16
3.4 Installation
Design the control box size, installing position of the gateway unit and cooling method of the control box in
such a way that the temperature around the gateway unit will not exceed 40°C.
Install the gateway unit vertically on a wall, as shown below, and provide a minimum clearance of 50mm
above and below the gateway unit and a minimum clearance of 100mm on the front for wiring.
For lateral installation such as installing multiple gateway units side by side, secure a sufficient space so that
the gateway unit is easily installed and removed.
If affection of heat or noise is a concern, take the measure into account.