4. POWER CABLING
4.3.1 CABLE AND FUSE SIZES
We recommend the fuse type gG/gL (IEC 60269-1). To make a selection of the fuse voltage rating, refer to the mains. Do not
use larger fuses than what is recommended Table 16.
Make sure that the operation time of the fuse is less than 0.4 seconds. The operation time agrees with the fuse type and the
impedance of the supply circuit. For more information on faster fuses, speak to the manufacturer. The manufacturer can also
recommend some aR (UL recognised, IEC 60269-4) and gS (IEC 60269-4) fuse ranges.
The table also shows the typical sizes and types of cables that can be used with the AC drive. In the selection of cables, refer to
local regulations, cable installation conditions and cable specification.
Table 16: The cable and fuse sizes for N800A
34
Frame
MR4
MR5
MR6
MR7
Type
0003 2—0004 2
0003 5—0004 5
0006 2—0008 2
0005 5—0008 5
0011 2—0012 2
0009 5—0012 5
0018 2
0016 5
0024 2
0023 5
0031 2
0031 5
0038 5
0048 2
0046 5
0062 2
0061 5
0075 2
0072 5
0088 2
0087 5
0105 2
0105 5
Mains, motor and
brake resistor*
cable Cu [
㎟
]
3*1.5+1.5
3*1.5+1.5
3*2.5+2.5
3*6+6
3*6+6
3*10+10
3*10+10
3*16+16 (Cu)
3*25+16 (Al)
3*25+16 (Cu)
3*35+10 (Al)
3*35+16 (Cu)
3*50+16 (Al)
3*35+16 (Cu)
3*70+21 (Al)
3*50+25 (Cu)
3*70+21 (Al)
Main terminal
[
㎟
]
Terminal cable size
1—6 solid
1—4 stranded
1—6 solid
1—4 stranded
1—6 solid
1—4 stranded
1—10 Cu
1—10 Cu
1—10 Cu
2.5—50 Cu/Al
2.5—50 Cu/Al
2.5—50 Cu/Al
6-70
㎟
Cu/Al
6-70
㎟
Cu/Al
6-70
㎟
Cu/Al
Earth termi-
nal
[
㎟
]
1—6
1—6
1—6
1—10
1—10
1—10
2.5—35
2.5—35
2.5—35
6-70
㎟
6-70
㎟
6-70
㎟
I
L
[A]
3.7—4.8
3.4—4.8
6.6—8.0
5.6—8.0
11.0—12.5
9.6—12.0
18.0
16.0
24.0
23.0
31.0
31.0
38.0
48.0
46.0
62.0
61.0
75.0
72.0
88.0
87.0
105.0
Fuse
(gG/gL)
[A]
6
10
16
20
25
32
40
50
63
80
100
125
N800A
Содержание N800 Series
Страница 2: ...ISSUEDATE 2015 06 26 VER 1 ...
Страница 3: ......
Страница 19: ...3 MOUNTING 3 2 2 WALL MOUNTING OF MR5 Fig 3 ThedimensionsoftheACdrive MR5 13 N800A ...
Страница 20: ...3 MOUNTING 3 2 3 WALL MOUNTING OF MR6 Fig 4 ThedimensionsoftheACdrive MR6 14 N800A ...
Страница 21: ...3 MOUNTING 3 2 4 WALL MOUNTING OF MR7 Fig 5 ThedimensionsoftheACdrive MR7 15 N800A ...
Страница 22: ...3 MOUNTING 3 2 5 WALL MOUNTING OF MR8 IP21 AND IP54 Fig 6 ThedimensionsoftheACdrive MR8 IP21andIP54 16 N800A ...
Страница 23: ...3 MOUNTING 3 2 6 WALL MOUNTING OF MR8 IP00 Fig 7 ThedimensionsoftheACdrive MR8 IP00 17 N800A ...
Страница 24: ...3 MOUNTING 3 2 7 WALL MOUNTING OF MR9 IP21 AND IP54 Fig 8 ThedimensionsoftheACdrive MR9 IP21andIP54 18 N800A ...
Страница 29: ...3 MOUNTING 3 3 1 FLANGE MOUNTING OF MR4 Fig 13 ThedimensionsoftheACdrive flangemounting MR4 23 N800A ...
Страница 30: ...3 MOUNTING 3 3 2 FLANGE MOUNTING OF MR5 Fig 14 ThedimensionsoftheACdrive flangemounting MR5 24 N800A ...
Страница 31: ...3 MOUNTING 3 3 3 FLANGE MOUNTING OF MR6 Fig 15 ThedimensionsoftheACdrive flangemounting MR6 25 N800A ...
Страница 32: ...3 MOUNTING 3 3 4 FLANGE MOUNTING OF MR7 Fig 16 ThedimensionsoftheACdrive flangemounting MR7 26 N800A ...
Страница 33: ...3 MOUNTING 3 3 5 FLANGE MOUNTING OF MR8 Fig 17 ThedimensionsoftheACdrive flangemounting MR8 27 N800A ...
Страница 34: ...3 MOUNTING 3 3 6 FLANGE MOUNTING OF MR9 Fig 18 ThedimensionsoftheACdrive flangemounting MR9 28 N800A ...
Страница 52: ...4 POWERCABLING 46 3 Removethecablecover MR8 MR9 N800A ...
Страница 53: ...4 POWERCABLING 47 4 Removethecableentryplate MR8 MR9 N800A ...
Страница 54: ...4 POWERCABLING 48 5 MR9only Loosenthescrewsandremovethesealingplate N800A ...
Страница 55: ...4 POWERCABLING 49 6 RemovetheEMCshieldplate A ThewingnutinMR8 A MR9 N800A ...
Страница 80: ...5 CONTROLUNIT 74 Fig 30 Thegalvanicisolationbarriers A Thecontrolunit B Thepowerunit N800A ...
Страница 84: ...6 COMMISSIONINGANDADDITIONALINSTRUCTIONS 78 3 FindtheEMCjumpersthatconnecttheRFIfilterstoground N800A ...
Страница 101: ......