1. SAFETY
1.4 EARTHING AND EARTH FAULT PROTECTION
The AC drive must always be earthed with an earth conductor that is connected to the earth terminal that is identified with the
symbol . Not using an earth conductor can cause damage to the drive.
The touch current of the drive is more than 3.5 mA AC. The standard EN 61800-5-1 tells that 1 or more of these conditions for
the protective circuit must be true.
The connection must be fixed.
a) The protective earth conductor must have a cross-sectional area of minimum 10
㎟
Cu or 16
㎟
Al. OR
b) There must be an automatic disconnection of the mains, if the protective earth conductor breaks. See chapter 4 Power
cabling. OR
c) There must be a terminal for a second protective earth conductor in the same crosssectional area as the first protective
earth conductor.
Table 2: Protective earthing conductor cross-section
The values of the table are valid only if the protective earthing conductor is made of the same metal as the phase conductors.
3
CAUTION!
Make sure that the EMC level of the AC drive is correct for your mains. See chapter 6.5 Installation in an IT system.
An incorrect EMC level can cause damage to the drive.
CAUTION!
Prevent radio interference. The AC drive can cause radio interference in a domestic environment.
NOTE!
If you activate the autoreset function, the motor starts automatically after an automatic fault reset. See the Ap-
plication Manual.
NOTE!
If you use the AC drive as a part of a machine, the machine manufacturer must supply a mains disconnection de-
vice (refer to EN 60204-1).
CAUTION!
Cross-sectional area of the phase conductors (S)
[
㎟
]
The minimum cross-sectional area of the protective
earthing conductor in question [
㎟
]
S
≤
16
S
16
≺
S
≤
35
16
35
≺
S
S/2
N800A
Содержание N800 Series
Страница 2: ...ISSUEDATE 2015 06 26 VER 1 ...
Страница 3: ......
Страница 19: ...3 MOUNTING 3 2 2 WALL MOUNTING OF MR5 Fig 3 ThedimensionsoftheACdrive MR5 13 N800A ...
Страница 20: ...3 MOUNTING 3 2 3 WALL MOUNTING OF MR6 Fig 4 ThedimensionsoftheACdrive MR6 14 N800A ...
Страница 21: ...3 MOUNTING 3 2 4 WALL MOUNTING OF MR7 Fig 5 ThedimensionsoftheACdrive MR7 15 N800A ...
Страница 22: ...3 MOUNTING 3 2 5 WALL MOUNTING OF MR8 IP21 AND IP54 Fig 6 ThedimensionsoftheACdrive MR8 IP21andIP54 16 N800A ...
Страница 23: ...3 MOUNTING 3 2 6 WALL MOUNTING OF MR8 IP00 Fig 7 ThedimensionsoftheACdrive MR8 IP00 17 N800A ...
Страница 24: ...3 MOUNTING 3 2 7 WALL MOUNTING OF MR9 IP21 AND IP54 Fig 8 ThedimensionsoftheACdrive MR9 IP21andIP54 18 N800A ...
Страница 29: ...3 MOUNTING 3 3 1 FLANGE MOUNTING OF MR4 Fig 13 ThedimensionsoftheACdrive flangemounting MR4 23 N800A ...
Страница 30: ...3 MOUNTING 3 3 2 FLANGE MOUNTING OF MR5 Fig 14 ThedimensionsoftheACdrive flangemounting MR5 24 N800A ...
Страница 31: ...3 MOUNTING 3 3 3 FLANGE MOUNTING OF MR6 Fig 15 ThedimensionsoftheACdrive flangemounting MR6 25 N800A ...
Страница 32: ...3 MOUNTING 3 3 4 FLANGE MOUNTING OF MR7 Fig 16 ThedimensionsoftheACdrive flangemounting MR7 26 N800A ...
Страница 33: ...3 MOUNTING 3 3 5 FLANGE MOUNTING OF MR8 Fig 17 ThedimensionsoftheACdrive flangemounting MR8 27 N800A ...
Страница 34: ...3 MOUNTING 3 3 6 FLANGE MOUNTING OF MR9 Fig 18 ThedimensionsoftheACdrive flangemounting MR9 28 N800A ...
Страница 52: ...4 POWERCABLING 46 3 Removethecablecover MR8 MR9 N800A ...
Страница 53: ...4 POWERCABLING 47 4 Removethecableentryplate MR8 MR9 N800A ...
Страница 54: ...4 POWERCABLING 48 5 MR9only Loosenthescrewsandremovethesealingplate N800A ...
Страница 55: ...4 POWERCABLING 49 6 RemovetheEMCshieldplate A ThewingnutinMR8 A MR9 N800A ...
Страница 80: ...5 CONTROLUNIT 74 Fig 30 Thegalvanicisolationbarriers A Thecontrolunit B Thepowerunit N800A ...
Страница 84: ...6 COMMISSIONINGANDADDITIONALINSTRUCTIONS 78 3 FindtheEMCjumpersthatconnecttheRFIfilterstoground N800A ...
Страница 101: ......