power supply setup
powermax
45
Operator Manual
2-5
extension cord recommendations
Use an extension cord of an appropriate wire size for the cord length and system voltage. Use a cord that meets national
and local codes.
The following tables provide the recommended gauge size for various lengths and input voltages. The lengths in the
tables are the length of the extension cord only; they do not include the power supply’s power cord.
Metric
Input voltage Phase
< 3 m
3–7.5 m
7.5–15 m
15–30 m
30 –45 m
208 VAC
1
10 mm
2
10 mm
2
10 mm
2
16 mm
2
25 mm
2
220 VAC
1
10 mm
2
10 mm
2
10 mm
2
16 mm
2
25 mm
2
200–240 VAC
1
10 mm
2
10 mm
2
10 mm
2
16 mm
2
25 mm
2
380 VAC
3
4 mm
2
4 mm
2
4 mm
2
6 mm
2
6 mm
2
400 VAC
3
4 mm
2
4 mm
2
4 mm
2
6 mm
2
6 mm
2
480 VAC
3
4 mm
2
4 mm
2
4 mm
2
6 mm
2
6 mm
2
english
Input voltage Phase
< 10 ft
10–25 ft
25–50 ft
50–100 ft
100–150 ft
208 VAC
1
8 AWG
8 AWG
8 AWG
6 AWG
4 AWG
220 VAC
1
8 AWG
8 AWG
8 AWG
6 AWG
4 AWG
200–240 VAC
1
8 AWG
8 AWG
8 AWG
6 AWG
4 AWG
380 VAC
3
12 AWG
12 AWG
12 AWG
10 AWG
10 AWG
400 VAC
3
12 AWG
12 AWG
12 AWG
10 AWG
10 AWG
480 VAC
3
12 AWG
12 AWG
12 AWG
10 AWG
10 AWG
Содержание POWERMAX 45
Страница 1: ...45 Plasma arc cutting system Operator Manual 805780 Revision 2 ...
Страница 6: ......
Страница 10: ...Table of Contents iv powermax45 Operator Manual ...
Страница 30: ...Power supply setup 2 8 powermax45 Operator Manual ...
Страница 74: ...operation 4 16 powermax45 Operator Manual ...
Страница 84: ...Maintenance and Repair 5 10 powermax45 Operator Manual ...