Install the steam manifold horizontal with it ensure a clean
steam out.
•
Maximum allowable pressure in the air duct is 1200 Pa.
For Hy05 and Hy08 the maximum allowable pressure is
1000 Pa.
•
On the return side, the maximum allowable negative air
pressure is 500 Pa. Placement of the steam manifold on
the supply side of the air duct is preferred.
•
With high-pressure air-conditioning systems, the unit's
drain hose system must be modified depending on the
over pressure. When this is the case please consult
HygroMatik.
•
Install the steam manifold as close as possible to the
steam humidifier in order to minimize steam loss through
condensation.
•
Shown installation and position dimensions are based on
experimental values. Special environmental conditions
could require adjustments.
•
Install a water drain within the absorption distance inside
the air duct.For steam bath applications: Install the steam
manifold safe from contact with people in order to prevent
injuries or burns. Do not install the steam manifold near a
temperature sensor or inaccurate readings may result.Air
flow rates over 3m/s can possibly lead to condensate
drainage problems at the steam manifolds which may
require adaptation measures.
Length of steam manifold [mm]*:
* special lenght on request
l
220
400
600
900
1200
1450
DN25
x
x
x
x
x
x
DN40
x
x
x
x
x
x
Please note
l
installed steam manifold