Page 27
Steam manifold
placement:
Horizontal installation of the steam manifolds is preferred. Howe-
ver, installation from below into the air duct is possible.
Air duct
Positioning of steam manifolds
Sample
flat
Staggered vertically and laterally
Air flow
very flat
By tilting the steam manifold 30 - 45°
towards the air flow direction, the mini-
mum upper clearance can be reduced
to 70mm.
min. distances: H1[mm] H2[mm]
30° 45°
DN25 182 168 225
DN40 193 179 230
very flat duct
narrow, high
Identical lenghts one on top of the other.
Staggered laterally if possible.
square
Identical lenghts, staggered vertically
and laterally
low, very
wide
facing each other
Vertical installation of
steam manifold