Page 34
5.9
Steam Solenoid Valves
When humidifying a number of loads, which are to be controlled
separately, using a single steam humidifier, steam solenoid
valves can be included in the steam hoses. Valve control has to
provided by the customer.
•
Install the vertical risers with flow from bottom to top
•
The best position is just above the steam humidifier
Steam solenoid valve installation principle
5.10
Unit Installation Check
Improper unit handling hazard!
This unit may only be brought
into operation by qualified personnel.
Before start-up, please check proper unit installation following
the list below:
Is the unit perpendicularly aligned in both the vertical
and horizontal axis?
Have all clearances been obeyed?
Does steam hose have a slope of 5-10%?
Is condensate hose installed with a loop of min. 200
mm?
Is steam manifold positioned correctly?
Are all bolts and clamps tightened?