Page 39
6.5
Water Treatment
For water treatment system specifications, use the following
table.
The figures below assume that the humidifier runs for 24 hours
at 100% output.
6.6
Water Discharge
Risk of scalding!
Wastewater must drain freely and pressureless!
During blow down up to 0.3 l/s are being drained with a tempera-
ture of about 95 °C.
Avoid contact in order not to burn skin.
For water discharge, we recommend installation of a flexible
water drain hose. Humidifier and waste water discharge must be
on the same pressure level.
Please note:
•
Do not bend the drain hose, respect length specification
•
For the discharge line and drain pipe, select materials
temperature-resistant up to 95 °C or use the „HyCool“
option
Install the water drain system as follows:
»
Install a drain hose 1 1/4 ", 250 - 1000 mm long, into a
pressureless outlet according to DIN EN 1717. Locate
the outlet sideways of the humidifier so that ascending
vapor does not condensate on the humidifier`s housing
Heater-
Compact
Max. Water Consump-
tion in 24 hrs [l]
02
55
03
83
06
166
09
248
12
331
18
497
27
745
Model
HC 02 - 27
HC 03 -10
1 x 1 1/4"