Page 20
Vertical steam manifold installation
Horizontal installation of the steam mani-
folds is preferable. However, vertical
installation into the air duct from below is
also possible.
Standard manifold dimensions [mm]/
[inch]***:
*** Special lengths on demand.
**** will be replaced in 2019 by 1500 mm / 59,1 inch long
steam distributors
Number and size
of the steam manifolds
available as well as the nominal diameter
of the repective steam and condensate
hoses may be taken from the table
below:
220/
8.7
400/
15.7
600/
23.6
900/
35.4
1200/
47.2
1450****/
57.1
Steam manifold arrangement
Steam supply
Air flow
direction
Model
Steam
manifold
Steam
hose
Conden-
sate
hose
FLH03-T
to
FLH15-T
1
x DN25/
1“
1
x DN25/
1“
1
xDN12/
1/2“
FLH25-T
1
xDN40/
1 1/2“
1
xDN40/
1 1/2“
1
xDN12/
1/2“
FLH40-T
FLH50-T
2
xDN40/
1 1/2“
2
xDN40/
1 1/2“
2
xDN12/
1/2“
FLH80-T
FLH100-T
4
xDN40/
1 1/2“
4
xDN40/
1 1/2“
4
xDN12/
1/2“
FLH03-TSPA
to
FLH25-TSPA
1
xDN40/
1 1/2“
1
xDN40/
1 1/2“
1
xDN12/
1/2“
FLH40-TSPA
FLH50-TSPA
2
xDN40/
1 1/2“
2
xDN40/
1 1/2“
2
xDN12/
1/2“
FLH80-TSPA
FLH100-T
4
xDN40/
1 1/2“
4
xDN40/
1 1/2“
4
xDN12/
1/2“
SLE02-
SLE15
1
x DN25/
1“
1
x DN25/
1“
1
xDN12/
1/2“
SLE20/
SLE30
1
xDN40/
1 1/2“
1
xDN40/
1 1/2“
1
xDN12/
1/2“
SLE45/
SLE65
2
xDN40/
1 1/2“
2
xDN40/
1 1/2“
2
xDN12/
1/2“