Page 53
600 V
Unit type
FLH06
FLH09
FLH15
FLH25
FLH30
Steam output [lb/h]
10,1 -
11,0
- 11,0
15,0 -
16,3
- 16,3
25,4 -
27,8
- 27,8
42,1 -
45,9
- 45,9
50,8 -
55,2
- 55,2
Electrical connection
(1)
Rated power [kW]
3,4 -
3,7
- 3,7
5,1 -
5,6
- 5,6
8,7 -
9,4
- 9,4
14,3 -
15,6
- 15,6
17,3 -
18,8
- 18,8
Nominal current [A]
5,9 -
6,2
- 6,2
8,9 -
9,3
- 9,3
8,7 -
9,1
- 9,1
14,4 -
15
- 15
17,4 -
18,1
- 18,1
Fuse [A]
3 x 20
Connection terminals max. [in²]
1,4
Number of steam cylinder
Control
Control voltage
(3)
Steam hose connection [in]
1 x 1,6
1 x 1,6
(6)
Water consumption
(7)
[usgal/h]
6
8,88
15,12
24,96
32,88
Water flow rate
(8)
[usgal/min]
1,08 / 6,16
Max. filling capacity [usgal]
9,5
Empty weight [lb]
88,2
Operation weight [lb]
168,7
Width
(9)
[in]
25,2
Height
(9)
[in]
30,9
Depth
(9)
[in]
16,5
Water connection
Drain water connection
12,6
fully demineralised water / cleaned condensate / partially softened
tap water of varying qualities
1 to 10 bar, for 3/4" external thread
Connection Ø 1 1/4"
21,1
27,4
18,1
(11)
21,3
44,1
59,5
55,8
91,5
0,34 / 5,42
0,74 / 5,81
1,3
3,7
1
FlexLine mainboard with capacitive 3.5" touch colour display
208 - 240V 0,5A
1 x 1,0
Technical data FlexLine Heater
575 -
600
- 600V /3Ph /50-60Hz
3 x 16
0,2
0,4
Unit type
FLH40
FLH50
FLH80
FLH100
Steam output [lb/h]
67,7 -
73,6
- 73,6
84,4 -
91,9
- 91,9
135,1 -
147,3
- 147,3
168,7 -
183,6
- 183,6
Electrical connection
(1)
Rated power [kW]
23 -
25
- 25
28,7 -
31,2
- 31,2
2 x
23 -
25
- 25
2 x
28,7 -
31,2
- 31,2
Nominal current [A]
23,1 -
24,1
- 24,1
29,7 -
30,1
- 31
2 x
23,1 -
24,1
- 24,1
2 x
29,7 -
30,1
- 31
Fuse [A]
3 x 30
3 x 35
2 x 3 x 30
2 x 3 x 35
Connection terminals max. [in²]
Number of steam cylinder
Control
Control voltage
(3)
Steam hose connection [in]
Water consumption
(7)
[usgal/h]
40,08
50,04
80,16
99,96
Water flow rate
(8)
[usgal/min]
Max. filling capacity [usgal]
Empty weight [lb]
Operation weight [lb]
Width
(9)
[in]
Height
(9)
[in]
Depth
(9)
[in]
Water connection
Drain water connection
(1)
Other voltages on request
(3)
Separate control voltage on request
(7)
Maximum water consumption at 100% demand plus blow down losses.
Water consumption depends on the water quality and options installed.
(8)
Flow rate of the feed water during refilling or pumping out. Unit without options / maximum rate with options.
(9)
Outer dimensions of width and depth. Height including drain connection
(11)
Units with production date January 2022 and earlier: 540 mm
16,5
fully demineralised water / cleaned condensate / partially softened
tap water of varying qualities
1 to 10 bar, for 3/4" external thread
Connection Ø 1 1/4"
2x Connection Ø 1 1/4"
SPA units (FLE05-FLE15) will be delivered with a steam hose connection of 1x1,6 inch.
25,2
46,1
30,9
88,2
176,4
168,7
334,9
Technical data FlexLine Heater
1,4
18,9
1
2
208 - 240V 0,5A
208 - 240V 1A
2 x 1,6
4 x 1,6
575 -
600
- 600V /3Ph /50-60Hz
FlexLine mainboard with capacitive 3.5" touch colour display
1,08 / 6,16
2 x / 1,08 / 6,16
9,5