Page 48
18. Malfunctions
Problem
Possible Cause
to do
No steam is coming
out of steam lance
•
Defective Hygrostat or humidity
sensor
•
Defective Control Valve
•
Defective Actuator
•
Inaccurate or defective control
•
Fouled or blocked coarse strainer in
the filter before separator
•
Shut-off valve in steam supply line
is closed.
•
Pressure reduction valve, if instal-
led, is out of order.
•
Check Hygrostaten and/or
humitiy sensor and repair
or replace as necessary.
•
Check valve and clean it
or replace as necessary.
•
Measure control signal.
Check, repair or replace
as necessary.
•
Check actuator, reset,
repair or replace.
•
Remove coarse strainer
and clean or replace.
•
Open shut-off valve
•
Clean pressure reduction
valve, possibly reset ope-
rational pressure.
Steam is coming
out of steam lance
although desired
humidity value is re-
ached.
•
Foreign objects between valve cone
and face prevent valve from closing
properly.
•
Defective or falsely set Hygrostat or
humidity sensor .
•
Actuator does not close properly.
•
Residual condensate evaporates in
the steam lance and exits the lance
as pressureless steam (re-evapora-
tion effect) This process can take up
to 20 minutes.
•
Check and clean valve
valve .
•
Check humidity or Hygros-
tat and re-set or repair.
•
Re-adjust actuator to cont-
rol valve.
•
Check out steam supply
pressure for the steam
lance heating system.
Supply steam lance hea-
ting system from a sepa-
rate dry steam steam
reservoir (max. 4 bar).
Condensate is co-
ming out of steam
lance
•
Improper steam supply installation
to the humidifier.
•
Defective or fouled steam trap eit-
her for separator or steam lance
heating system.
•
Back pressure from condensate
network is higher than the operating
steam injection humidifier pres-
sure.
•
Check Installation.
•
Clean or replace steam
trap.
•
Reduce pressure in the
condensate return line.
•
If this is not possible, con-
nect steam trap to sepa-
rate return line.
Содержание DDS20
Страница 1: ...Steam Injection Humidifiers DDS for existing steam nets DDS ENZ DDS EN Manual...
Страница 25: ...Page 25 13 3 Separator Type 20 with one steam lance KVS Value m h Pressure bar Steam Output kg h Lance code...
Страница 27: ...Page 27 13 5 Separator Type 40 with one steam lance KVS Value m h Pressure bar steam output kg h Lance code...
Страница 55: ......
Страница 56: ...12 2004...