15.3 Separators
Warning:
Before installation, check out the steam supply piping.
It must be established that the steam humidifier is su pplied with
as dry a steam as possible (steam with as little condensate as
possible).
Steam pressure at the separator entry point must not exceed 4
bar.
Steam humidifier operating pressure must be kept at a constant
level. It is possible th at in o rder to ge nerate contsant pressure,
pressure reduction stations may be required.
It must be guaranteed the steam supplying the steam humidifier
is as dry as possible. Check that the steam supply lines are
equipped with the necessary condensate drains.
The supply line for the steam humidifier must be taken from the
highest point in the main supply line.
Install a filter in the steam supply line direct ly in fron t of every
humidifier. This is the only way to ensure that no foreign objects
can find their way into the humidification unit.
Keep the piping connections as shor t as po ssible. In this way
the energy losses are reduced, the system can heat up quicker,
condensates are minimised and the system overall efficiency is
increased.