Page 47
»
Screw down new complete float unit (E-C) with valve
screws (D) .
»
Screw down cover with new seal (T).
Use HygroMatik spare parts number E-4111834
Exchanging air vent
»
Loosen C spring clamp (L).
»
Remove capsule element (H) and spacer (M).
»
Unscrew valve seat (J) (SW17).
»
Screw down valve holder (N), new seal (B), with new
valve seat (J).
»
Fit in spacer (M) and capsule unit (H).
»
Fit spring clamp (L).
Use HygroMatik part number E-4111836
17.4 Thermostatic Cap sule S team t rap t ype
MST21
Warning:
Before b eginning an y mainte nance operat ion make
sure that the feed and drain are shut off and that the unit is cool
under not under pressure.
Replacing Capsule Element Set
»
When the unit is cold, unscrew cover using a SW 22 or
SW 32 wrench.
»
Remove strainer (A), spring (B), capsule (C) and
spacer (D).
»
Apply a light coating of sealing paste to the cap threads.
»
Assemble new capsule element set in the proper
sequence.
»
Note: cap torque specifications: 110 Nm.
»
Check steam injection unit for correct functioning.
»
Start up unit and operate for 15 minutes ideally at maxi-
mum output.
»
Check safety features.
»
Check pipe connections for possible leakage.
Use HygroMatik part number E-4111828.