Page 49
Warning:
The unit must be switched off immediately if it is mal-
functioning. Malfunctions may only be repaired by qualified per-
sonnel under observation of all safety instructions.
Problem
Possible Cause
to do
Condensate is co-
ming out of steam
lance.
•
Steam trap drain is considerably
higher that the DDSystem.
•
Start-up safety feature does not
work properly.
•
Defective or unsuitable thermostatic
capsule condensate drain attached
to steam lance heating system.
•
Steam heating for steam lance hea-
ting system insufficient.
•
Install condensate drain
beneath the humidifier
level and pump out the
resultant condensate to a
suitable place.
•
Check wiring and function
of start-up safety feature.
•
Check out condensate
drain and integrated ele-
ments. Type E must be
used. Clean condensate
drain.
•
Optimum heating effect
occurs from pressure over
1 bar. Less pressure can
lead to lengthier pre-hea-
ting times.