Error messages / troubleshooting
FAM 15/30/50/70 ATEX
en(us)
Page 55 / 96
BeWa FAM15-70 Atex 3193049h en(us) 2013-06-19
2013-06-19
[H10] Change fluid filter
Step
Description
Malfunction:
"Replace fluid filter"
1.
Press the RESET button to acknowledge/reset the fault.
2.
Switch off the unit at the main switch.
3.
Close the ball cocks on the IN and OUT connections.
4.
Empty the filter housing via the drain ball valve.
5.
Replace the filter element according to the description on page
69.
6.
Open the ball cocks on the IN and OUT connections.
7.
Switch on the unit at the main switch.
8
Does the malfunction repeat after ~ 4 minutes?
-> a. Yes
-> proceed to Step 10.
9.
-> b. No
-> proceed to Step 11.
10.
Check the differential pressure switch and the feed lines.
11.
The fault is repaired.