HPT 500 IO-Link
13
Edition: 2020-04-08
HYDAC ELECTRONIC GMBH
Part no.: 670038
o
Switching delay (Subindex 5):
Switching delay in ms for switching into the active condition.
o
Switch-back delay (Subindex 6):
Switch-back delay in ms to switch in to the inactive condition.
Filter constant pressure (Index 132):
Time constant in ms, via which the measured
values are averaged. Time constant below the sample rate of 2 ms do not have any
impact, if time constant = 0, the filter is switched off.
The filter is a first-grade low pass.
10.5 Device information and diagnostic options
(read only)
This new generation of further developed sensors detects further relevant information (in
addition to the operation data):
Name of manufacturer (Index 16):
HYDAC ELECTRONIC GMBH
Product name (Index 18):
Type designation, i.e. HPT 506-F31-02.0-A-000
Product ID (Index 18):
Part number, i.e. 927692
Serial number (Index 21)
Hardware version (Index 22)
Firmware version (Index 23)
Error counter (Index 32)
Device status (Index 36):
- (0) Device is OK
- (1) Maintenance
required
- (2) Beyond
specification
- (3) Function
test
- (4) Error
- [5..255]
Reserved
Detailed device status (Index 37):
Process data input (Index 40))
Pressure (Index 112):
Process values of the pressure since reset. Reset is possible
using standard command 164.
o
Current measured value (Subindex 1):
Current pressure value (filtered) in bar, with 3 decimals
o
Min value (Subindex 2):
Min pressure value (filtered) in bar, with 3 decimals
o
Max value (Subindex 3):
Max pressure value (filtered) in bar, with 3 decimals
Device temperature (Index 127):
Process values of the device temperature since
reset. Reset using standard command 164.
o
Current measured value (Subindex 1):
Current device temperature value in °C with 1 decimal place.
o
Minimum value (Subindex 2):
Minimum device temperature value in °C with 1 decimal place.
o
Maximum value (Subindex 3):
Maximum device temperature value in °C with 1 decimal place.