Steckerbelegung [Pin Assignment]
Printed in the Federal Republic of Germany
HYDAC –ELECTRONICGMBH , All Rights Reserved
Stand:21.07.2010
Mat. Nr. 669792
Page 22 of 36
HLT 2100-R1-P61-PRO-… / HLT 2500-Lx-P61-PRO-...
Signal output Profibus, female connector M12x1, 5-pin + male connector M12x1, 5-pin + male connector M8, 4-pin
General note:
If the measuring system constitutes the last step in the Profibus segment, the bus must be terminated according to
the PROFIBUS-standards.
HYDAC-ELECTRONIC recommends the exclusive use of bus cables certified by the Profibus User Organization
(PNO) prescribed for operation.
The shielding must be connected to the mating connector housing with a
large contact surface!
By means of the BCD address switches
S1 (10
0
)
and
S2 (10
1
)
the station addresses from 1 to 99 for the
Profibus are set.
X1
Male socket, (M12x1-5 pol. B-coded)
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Screwed gland
N.C.
Profibus, Data A
N.C.
Profibus, Data B
N.C.
Shielding
Profibus_IN
X2
Female socket, (M12x1-5 pol. B-coded)
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Screwed gland
VP, +5 V DC
Profibus, Data A
DGND
Profibus, Data B
N.C.
Shielding
Profibus_OUT
or termination between
Pin 1 and Pin 3
X3
Male socket, (M8x1-4 pol.)
Pin 1
Pin 2
Pin 3
Pin 4
19 – 27 V DC brown
TRW white
GND, 0V
blue
TRWinProg – black
Supply Voltage /
TRWinProg (for service only) or
connection of an external
display TA-MINI