background image

Damocles2

Damocles2

Damocles2

40

41

Tip:

  

For detailed description of the e-mail format, see the “Using Damocles2 units in your programs” section: 

http://hw-group.us/cs/podpora/kba004-pouziti-damocles2-ve-vasich-programech

GSM

Sekce Serial Port Settings

Port Function

 – sets the serial port function (only for models with a serial port and the netGSM 

server side feature). 3 options are available: 
• 

Disabled

 – Serial port is off. Only if no modem is connected and the device works as the client side.

• 

GSM modem

 – A GSM modem is connected, and Damocles2 also acts as a netGSM server.

Remote SMS gateway

Configures the IP address, HTTP port and path to the service for sending SMS requests.

For Damocles2, the path is always service.xml

.

Received e-mail example: 

DATE TIME Device_NAME Device_IP

01.09.2016 13:42:19 Damocles2 1208 192.168.100.55
Email initiated: Test 
------------------------------------------------------------

ID SENSOR_Name VALUE UNIT Safe_RANGE ALARM

------------------------------------------------------------
ALARM state:

-------------------------------------------------------

    1 Binary 1 ON if ON
Sensors list:

--------------------------------------------------

1 Binary 1 OFF Disabled

2 Binary 2 OFF Disabled

3 Binary 3 OFF Disabled

4 Binary 4 OFF Disabled

5 Binary 5 OFF Disabled

6 Binary 6 OFF Disabled

7 Binary 7 OFF Disabled

8 Binary 8 OFF Disabled

9 Binary 9 OFF Disabled

10 Binary 10 OFF Disabled

11 Binary 11 OFF Disabled

12 Binary 12 OFF Disabled

123 Comm Monitor 1 OFF Disabled

151 BinOut 1 OFF Manual 

152 BinOut 2 OFF Manual 

153 BinOut 3 OFF Manual 

154 BinOut 4 OFF Manual 

155 BinOut 5 OFF Manual 

156 BinOut 6 OFF Manual 

157 BinOut 7 OFF Manual 

158 BinOut 8 OFF Manual 

1151 VirtBinOut 1 OFF Manual 

1152 VirtBinOut 2 OFF Manual 

1153 VirtBinOut 3 OFF Manual 

1154 VirtBinOut 4 OFF Manual 

1155 VirtBinOut 5 OFF Manual 

1156 VirtBinOut 6 OFF Manual 

1157 VirtBinOut 7 OFF Manual 

1158 VirtBinOut 8 OFF Manual 
-------------------------------------------------------------------

Damocles2 1208: http://192.168.100.55 00:0A:59:04:40:E0

-------------------------------------------------------------------

Web interface

Web interface

Tip:

  

It is not always necessary to con-
figure a SMTP Server in order to 
send e-mails. Damocles2 can 
work as SMTP server itself and 
deliver the e-mails directly to the 
user’s mailbox.    

 

However, always test this mode in 
your particular environment – the 
e-mails sent in this mode are 
often blocked by various spam 
filters due to missing reverse MX 
records.    
Damocles2 can only send e-mails, 
it cannot receive them.

E-mail is sent upon every alarm 
activation and deactivation. 

Sending a test e-mail

Multiple systems need to be con-
figured correctly in order to send 
e-mails from the device success-
fully. Therefore, it is advisable to 
double-check the following para-
meters:
•  

Gateway

 in the network settings.

•  

DNS server

 in the network settings. 

•  

SMTP server

 and port.

•  

Authentication

 turned on, correct 

name

 and 

password

.

•  

Spam filter

 of your mailbox tur-

ned off.

To send e-mail, check:

1. Correct 

Gateway IP

 address

2.  

DNS server

 in the network 

settings

3. 

SMTP server

 and port

4.  

Authentication

 enabled, correct 

username

 and 

password

5.  

Spam filter

 for your mailbox 

is disabled

Содержание Damocles2 1208

Страница 1: ...Damocles2 User manual...

Страница 2: ...epublic and the European Union The device has been tested and is supplied in working order To keep the de vice in this condition it is necessary to adhere to the following safety and maintenance instr...

Страница 3: ...IN1 IN1 NC1 COM1 NO1 NO2 NC2 COM2 Outputs Setup Safe Ethernet GND U Power 9 30V Damocles2 1208 SETUP SAFE IN1 GND IN2 IN3 GND IN4 IN5 GND IN6 IN7 GND IN8 IN9 GND IN10 IN11 GND IN12 GND GND GND GND GN...

Страница 4: ...e upload Yes Yes Yes Modbus TCP Yes Yes Yes HWg PUSH SensDesk protocol Yes Yes Yes NotGSM SMS GW protocol Yes Yes Yes Box 2 Box 4 SNMP protocol for VDO Yes Yes Yes Box 2 Box 16 HTTP protocol for VDO Y...

Страница 5: ...de of the safe range flashing means TCP or Serial Setup mode DIP1 DIP2 switches DIP1 activates serial setup mode restores factory defaults To restore factory defaults quickly toggle the switch 3 withi...

Страница 6: ...e of the device Enter the device IP address in a web browser Click the IP address in UDP Config Click the underlined IP address in UDP SETUP The WWW page displays current status of the device and its...

Страница 7: ...l General Setup Security SNMP Modbus E mail GSM Log Time Portal Inputs Outputs Virtual Outputs System Overview of current readings IP address DNS IP filter security username password HTTPS certificate...

Страница 8: ...evice 2 HTTPS certificates 3 Note For a detailed description see the detailed web interface description 2nd half of the manual Changes SNMP protocol versions 1 SNMP 5 destinations for SNMP Traps 2 Not...

Страница 9: ...network settings 3 SMTP server and port 4 Authentication enabled correct username and password 5 Spam filter for your mailbox is disabled E mail This text is inserted at the beginning of the e mail s...

Страница 10: ...r whenever a change in a sensor value exceeds the configured AutoPush value Connection parameters for the www SensDesk com portal are pre filled AutoPush configuration Whenever an input state changes...

Страница 11: ...put 1 1 2 3 Pulse Timer When set the output is activated only for a specified duration Pulse Timer 0 disables this function For details see the WEB interface description Output mode A Manual DO can be...

Страница 12: ...ry 60s For more information see Web interface Virtual Outputs System Restores factory defaults 1 Uploads new firmware from the PC 2 Configuration Download download the configuration from the device to...

Страница 13: ...tacts read as 1 On resistance against the Common pin must not exceed 500 Specifications Maximum wiring length 50m Supported sensors Any contact without external voltage dry contact Alarm settings for...

Страница 14: ...or TCP Setup Ability to restore factory defaults Detailed program description as well as an instructional video clip are available on the CD supplied with the device or at our website http www hw grou...

Страница 15: ...be used for example to read energy consumption meters with a pulse output S0 Counters are incremented whenever the input is closed The pulse must be longer than 20 ms to be registered Outputs Displays...

Страница 16: ...p events E mailing SMTP Logging of values with timestamps IPV6 This block groups options for operation in networks that support IPv6 Enable IPV6 Enables IPv6 support Autoconfig IP parameters Enables a...

Страница 17: ...fy the restrictions resulting from the respective security settings No restrictions default HW protection DIP On User Password IP Access filter SNMP Communities Read only Read Outputs Read Write HTTP...

Страница 18: ...ts feature Toggle DIP1 several times during the first 5 seconds after powering up the device HTTPS Server Certificate files Used to manage certificates needed for the HTTPS server Allows you to upload...

Страница 19: ...e communication Available options are DES and AES Privacy Password Password key for encrypting the communication MIB II System Group User defined data in the standard SNMP header SysContact Contact in...

Страница 20: ...Name Username for authentication with the SMTP server Password Password for authentication with the SMTP server E mail Subject Text Subject of the e mails sent followed by the default e mail text see...

Страница 21: ...53 BinOut 3 OFF Manual 154 BinOut 4 OFF Manual 155 BinOut 5 OFF Manual 156 BinOut 6 OFF Manual 157 BinOut 7 OFF Manual 158 BinOut 8 OFF Manual 1151 VirtBinOut 1 OFF Manual 1152 VirtBinOut 2 OFF Manual...

Страница 22: ...its in your programs section http hw group us cs podpora kba004 pouziti damocles2 ve vasich programech Note Any changes must be confirmed by clicking the Apply Changes button A successful change is in...

Страница 23: ...ports when there is no active communication Note The clock does not run when the device is powered off The device contains no battery After a power failure the time will be synchronized with the SNTP...

Страница 24: ...ining time before the next standard data upload Current Log Timer Indicates the remaining time before the next caching of data Current Check Timer Indicates the time remaining until the next Check Pus...

Страница 25: ...sending data to the MQTT broker Topic Prefix Name MQTT Topic adress prefix Inputs Topic Name Corresponds to the input name at the Inputs tab ID Corresponds to the input ID at the Inputs tab Publish En...

Страница 26: ...beginning and alarm end Out of Safe Range Response to the Alarm state activation deactivation for dry contact inputs SNMP Trap Enables sending a SNMP trap upon alarm activation deactivation E mail Ena...

Страница 27: ...fter confirming with Apply Changes Local Condition Output is controlled using a condition and a sensor The output state is read only for M2M protocols output cannot be controlled The control is linked...

Страница 28: ...t the Outputs tab at the remote side Username Password If the remote side uses SW protection against unauthorized use enter the Read Write or the Read Outputs password System Communication monitor Mon...

Страница 29: ...application runs in the background NTservice Data is retrieved from the devices over http or e mail Data can be exported over XML or automatically stored to MS Excel HWg Trigger Windows application f...

Страница 30: ...0 27 Server room 366985520 France Rue des Champolains 29 Auxerre 48 2 RH 10 30 26 Showroom 302871441 Italy Via Marco Claudio 778 Terni 0 none unit 10 30 25 Storage 652924144 Sweden Nyborgsgatan Arvids...

Страница 31: ...n after power disconnection Max distance Up to 50m LED Power RJ45 Green power OK Link Activity RJ45 Green physical connection established Yellow flashes communication taking place Input Output Status...

Страница 32: ...y RJ45 Green physical connection established Yellow flashes communication taking place Input Output Status Green input Yellow output Alarm On Setup Flashing Parameters Power 9 30V 1 7W DC Power connec...

Страница 33: ...Dry Contact Sensitivity 1 On 0 500 Up to 12V can appear at the socket against GND Pulse counter 24 32 bit min pulse width 20ms Counter value is retained even after power disconnection Max distance Up...

Страница 34: ...dnotkach poseidon2 a damocles2 HTTPS in Damocles2 and Poseidon2 http hw group us cs podpora kba003 https v jednotkach poseidon2 a damocles2 Formats and interfaces Formats and interfaces Poseidon2 4002...

Страница 35: ...HW group s r o Formansk 296 Prague 149 00 Czech Republic Phone 420 222 511 918 Fax 420 222 513 833 www HW group com...

Отзывы: