Damocles2
Damocles2
Damocles2
24
25
Common features of the Damocles2 family
Displayed readings
• Damocles2 displays current values of all digital inputs (DI).
• Inputs feature pulse counters for connecting energy meters with S0 outputs.
• An input is considered active (for Alarm state purposes) if it is closed for more than approx.
900ms (inputs are sampled approximately every 30 ms because of S0).
• Alarm state can be set independently for each input (contact).
• If the Alarm is not assigned to any channel (SMS, Email, SNMP Trap), the alarm is not notified
and the corresponding line is highlighted in yellow at the first page (General).
• Upon Alarm, the device can send a SNMP Trap, E-mail, or SMS.
• Damocles2 notifies both the beginning and the end of an alarm (contact closing and contact
opening).
• Supports a shared HWg-SMS-GW3 gateway for texting.
• Supports SNMPv1 and SNMPv3.
• Supports e-mail authentication via TLS.
Supported interfaces (in detail)
Supported interfaces (in detail)
DI (Digital Inputs) – Dry contact Inputs
Dry (voltage-free) contacts can be connected to these terminals. For example door contacts.
The inputs are electrically connected to the power supply.
• Unconnected inputs read as “
0 (Off)
”.
• Activated inputs (closed contacts) read as “
1 (On)
”, resistance against the Common pin must
not exceed 500
Ω
.
Specifications:
•
Maximum wiring length:
50 m
•
Supported sensors:
Any contact without external voltage (dry contact)
•
Alarm settings for each DI:
• Alarm inactive
• Alarm when the contact is open or closed
• Alarm when the contact is open
•
Possible alarm responses:
Common setting for all inputs
• No response
• Alarm alert sent as a SNMP trap
• Alarm alert sent by e-mail or text message (SMS)
• Alarm alert sent as a SNMP trap as well as by e-mail or SMS
•
Polling period:
approx. 900 ms
•
Range of sensor IDs:
DI (Digital Inputs) use ID addresses from 1 to 24
•
Input names:
Each DI can be named using up to 12 characters
•
Disconnected detector indication:
None, disconnected detectors read as “
O (Off)
”
DO (Digital Outputs)
Damocles2 units feature various types of digital outputs:
•
Damocles2 MINI
– Relay
•
Damocles2 1208
– Open Colector
•
Damocles2 2404
– Relay
Relay Output
Each output controls two relay contacts: one “
Normally Open
”
(NO)
contact (open when the
power is off and after startup), and one “
Normally Closed
”
(NC)
contact (closed when the power
is off and after startup).
Contact state (closed / open) is indicated by the corresponding LED.
The picture shows an example of connecting a 12 V light bulb, powered from the same source as the unit and controlled
by the Normally Open contact of output No. 4.
Common features of the Damocles2 family
NC COM NO
COM
Power
12V Power
30
NO
29