TP48200A-DT19C1, TP48200A-DT19C2,
TP48200A-HT19C1 and TP48200A-HT19C2 Telecom
Power
User Manual
4 Maintenance
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
53
4.2 Rectifying Common Faults
4.2.1 AC Failure
Possible Causes
The AC input power cable is faulty.
The AC input circuit breaker is OFF.
The power grid is faulty.
Measures
1.
Check whether the AC input cable is loose. If so, secure the AC input cable.
2.
Check whether the AC input circuit breaker is OFF. If so, handle the fault which caused
the AC input circuit breaker to turn OFF and then switch on the circuit breaker.
3.
Check whether the AC input voltage is lower than 50 V AC. If so, handle the power grid
fault.
4.2.2 AC Over Volt
Possible Causes
The AC overvoltage alarm threshold is incorrectly set on the SMU.
The power grid is faulty.
Measures
1.
Check whether the AC overvoltage alarm threshold is correctly set. If not, set the
threshold to the correct value.
2.
Check whether the AC input voltage exceeds the AC overvoltage alarm threshold (280 V
AC by default). If so, handle the AC input fault.
4.2.3 AC Under Volt
Possible Causes
The AC undervoltage alarm threshold is incorrectly set on the SMU.
The power grid is faulty.
Measures
1.
Check whether the AC undervoltage alarm threshold is correctly set. If not, set the
threshold to the correct value.
2.
Check whether the AC input voltage is below the AC undervoltage alarm threshold (180
V AC by default). If so, handle the AC input fault.
4.2.4 DC Over Volt
Possible Causes
The DC overvoltage alarm threshold is incorrectly set on the SMU.