C Associations Between Alarms and Dry Contacts on the
UIM
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
102
C
Associations Between Alarms and Dry
Contacts on the UIM
Table C-1
Associations between alarms and dry contacts
Port Type
Silk Screen
Associated Alarm
Dry contact input
DIN1
Dry contact input 1
DIN2
Dry contact input 2
DIN3
Dry contact input 3
DIN4
Dry contact input 4
DIN5
Dry contact input 5
DIN6
TP48200A-DT19C1 and TP48200A-DT19C2:
TEC Alarm
TP48200A-HT19C1 and TP48200A-HT19C2:
TCUA Alarm
Dry contact output
The default setting (closed:
alarm; open: normal) can be
modified.
ALM1
Mains faults
ALM2
DC overvoltage and undervoltage
ALM3
Rectifier faults
ALM4
AC surge protective device (SPD) faults or DC
SPD faults
ALM5
Battery or load fuse blown
ALM6
Excessively high or low ambient and battery
temperatures
ALM7
Door status alarm
ALM8
Fan faults