ID
Name
Severity Cause
Solution
2072
Transient
AC
overvolta
ge
Major
Cause ID = 1
The SUN2000 detects that
the phase voltage exceeds
the transient AC
overvoltage protection
threshold.
1. If the voltage at the grid
connection point is too high,
contact the local power
operator.
2. If you have confirmed that
the voltage at the grid
connection point exceeds the
upper threshold and obtained
consent from the local power
operator, modify the
overvoltage protection
thresholds.
3. Check whether the peak grid
voltage exceeds the upper
threshold.
2077
Off-grid
output
overload
Major
Cause ID = 1/2
The output is overloaded
or short-circuited.
1. Check whether the device
output is short-circuited.
2. Check whether the device
load configuration exceeds
the rated value.
SUN2000-(3KTL-10KTL)-M1
User Manual
8 Maintenance
Issue 02 (2020-11-20)
Copyright © Huawei Technologies Co., Ltd.
92